Back to the backflow review queue

Backflow assembly test: Riverside Dental

Approved

Filed Sep 28, 2026 by Casey Whitcomb, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 28, 2026
Assembly type
RP
Serial number
A957460
Size
1 1/2
Test gauge serial
G-7970
Gauge calibration date
Jun 10, 2026
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 073-36-01174
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5094 Turkey Hill Rd
Owner: Marsh Holdings LLC
Parcel 073-36-01174