Backflow assembly test: Maple Leaf Diner

Approved

Filed Oct 28, 2024 by Alex Benton, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 28, 2024
Assembly type
RP
Serial number
B232333
Size
4
Test gauge serial
G-7462
Gauge calibration date
Feb 8, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 073-89-01279
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.