Back to the backflow review queue

Backflow assembly test: Maple Leaf Diner

Approved

Filed Oct 9, 2025 by Casey Whitcomb, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 9, 2025
Assembly type
RP
Serial number
B232333
Size
4
Test gauge serial
G-2236
Gauge calibration date
Dec 29, 2024
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 073-89-01279
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5107 Turkey Hill Way
Owner: Pruitt Holdings LLC
Parcel 073-89-01279