Back to the backflow review queue

Backflow assembly test: Golden Animal Hospital

Approved

Filed May 2, 2025 by Drew Harlow, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 2, 2025
Assembly type
RP
Serial number
B728330
Size
4
Test gauge serial
G-8013
Gauge calibration date
Jan 31, 2025
Check valve 1
3.2 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Harlow, current on the service date
  • All required fields present
  • Address matches parcel 073-66-01297
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4157 Laurel Trl
Owner: Nguyen Holdings LLC
Parcel 073-66-01297