Backflow assembly test: 8006 Cedar Hollow Trl

Approved

Filed Oct 9, 2026 by Casey Whitcomb, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 9, 2026
Assembly type
RP
Serial number
W814661
Size
1
Test gauge serial
G-5148
Gauge calibration date
Dec 19, 2025
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 073-47-01177
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.