Backflow assembly test: 9018 Old Church Ln

Approved

Filed Aug 8, 2024 by Casey Whitcomb, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 8, 2024
Assembly type
PVB
Serial number
K354869
Size
3/4
Test gauge serial
G-2546
Gauge calibration date
Oct 25, 2023
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 073-49-01167
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9018 Old Church Ln
Owner: Hayden Kessler
Parcel 073-49-01167