Backflow assembly test: 9018 Old Church Ln
ApprovedFiled Aug 8, 2024 by Casey Whitcomb, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 8, 2024
- Assembly type
- PVB
- Serial number
- K354869
- Size
- 3/4
- Test gauge serial
- G-2546
- Gauge calibration date
- Oct 25, 2023
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Casey Whitcomb, current on the service date
- All required fields present
- Address matches parcel 073-49-01167
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.