Back to the backflow review queue

Backflow assembly test: 666 Mill Creek Rd

Approved

Filed Jan 28, 2024 by Drew Harlow, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 28, 2024
Assembly type
RP
Serial number
K642242
Size
3/4
Test gauge serial
G-2114
Gauge calibration date
Apr 3, 2023
Check valve 1
7.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Harlow, current on the service date
  • All required fields present
  • Address matches parcel 073-15-01278
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

666 Mill Creek Rd
Owner: Casey Ellery
Parcel 073-15-01278