Back to the backflow review queue

Backflow assembly test: 666 Mill Creek Rd

Approved

Filed Jan 30, 2025 by Drew Harlow, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 30, 2025
Assembly type
RP
Serial number
K642242
Size
3/4
Test gauge serial
G-5318
Gauge calibration date
Nov 22, 2023
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
1.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Harlow, current on the service date
  • All required fields present
  • Address matches parcel 073-15-01278
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

666 Mill Creek Rd
Owner: Casey Ellery
Parcel 073-15-01278