Backflow assembly test: 7950 Spring Branch Ln

Approved

Filed May 15, 2025 by Alex Benton, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 15, 2025
Assembly type
PVB
Serial number
B354579
Size
3/4
Test gauge serial
G-4322
Gauge calibration date
May 17, 2024
Check valve 1
0 psid
Check valve 1 closed tight
No
Check valve 2
1.7 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 073-16-01229
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

7950 Spring Branch Ln
Owner: Drew Harlow
Parcel 073-16-01229