Back to the backflow review queue

Backflow assembly test: Maple Leaf Pizza

Approved

Filed May 6, 2026 by Alex Benton, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 6, 2026
Assembly type
RP
Serial number
A300720
Size
1 1/2
Test gauge serial
G-8381
Gauge calibration date
Mar 4, 2026
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 073-56-01056
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8339 Stone Gate Rd
Owner: Benton Holdings LLC
Parcel 073-56-01056