Back to the backflow review queue

Backflow assembly test: 6536 Laurel Trl

Approved

Filed Jan 23, 2024 by Morgan Marsh, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 23, 2024
Assembly type
RP
Serial number
B674457
Size
3/4
Test gauge serial
G-4526
Gauge calibration date
Sep 3, 2023
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Morgan Marsh, current on the service date
  • All required fields present
  • Address matches parcel 073-91-01003
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6536 Laurel Trl
Owner: Taylor Vance
Parcel 073-91-01003