Back to the backflow review queue

Backflow assembly test: 5738 Pine Knoll Trl

Approved

Filed May 29, 2025 by Casey Whitcomb, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 29, 2025
Assembly type
DC
Serial number
K701638
Size
3/4
Test gauge serial
G-4423
Gauge calibration date
Aug 21, 2024
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Casey Whitcomb, current on the service date
  • All required fields present
  • Address matches parcel 073-31-01348
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5738 Pine Knoll Trl
Owner: Reese Vance
Parcel 073-31-01348