Back to the backflow review queue

Backflow assembly test: 195 Cedar Hollow Dr

Approved

Filed Mar 26, 2025 by Alex Benton, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 26, 2025
Assembly type
DC
Serial number
W201471
Size
1
Test gauge serial
G-3436
Gauge calibration date
Jan 14, 2025
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 073-47-01248
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

195 Cedar Hollow Dr
Owner: Emerson Fairley
Parcel 073-47-01248