Back to the backflow review queue

Backflow assembly test: Golden Taqueria

Approved

Filed Oct 20, 2025 by Alex Benton, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 20, 2025
Assembly type
RP
Serial number
A448188
Size
1 1/2
Test gauge serial
G-8267
Gauge calibration date
Mar 25, 2025
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Alex Benton, current on the service date
  • All required fields present
  • Address matches parcel 073-36-01345
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7087 Sycamore Ct
Owner: Calloway Holdings LLC
Parcel 073-36-01345