Backflow assembly test: Maple Leaf Animal Hospital

Approved

Filed Apr 22, 2024 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 22, 2024
Assembly type
DC
Serial number
K244272
Size
4
Test gauge serial
G-7162
Gauge calibration date
Sep 7, 2023
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-80-01056
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2596 Orchard Rd
Owner: Fairley Holdings LLC
Parcel 005-80-01056