Back to the backflow review queue

Backflow assembly test: Main Street Apartments

Approved

Filed Sep 11, 2026 by Taylor Vance, Northstar Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Sep 11, 2026
Assembly type
RP
Serial number
B407138
Size
1 1/2
Test gauge serial
G-9311
Gauge calibration date
May 7, 2026
Check valve 1
4.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Vance, current on the service date
  • All required fields present
  • Address matches parcel 005-19-01116
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1462 Orchard Dr
Owner: Wexler Holdings LLC
Parcel 005-19-01116