Back to the backflow review queue
Backflow assembly test: 2527 Old Church Way
ApprovedFiled Nov 10, 2026 by Taylor Vance, Northstar Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 10, 2026
- Assembly type
- RP
- Serial number
- W164194
- Size
- 1
- Test gauge serial
- G-5095
- Gauge calibration date
- Sep 13, 2026
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 1.1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Vance, current on the service date
- All required fields present
- Address matches parcel 005-58-01333
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2527 Old Church Way
Owner: Drew Ramirez
Parcel 005-58-01333