Backflow assembly test: 2527 Old Church Way

Approved

Filed Nov 10, 2026 by Taylor Vance, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Nov 10, 2026
Assembly type
RP
Serial number
W164194
Size
1
Test gauge serial
G-5095
Gauge calibration date
Sep 13, 2026
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
1.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Vance, current on the service date
  • All required fields present
  • Address matches parcel 005-58-01333
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.