Backflow assembly test: Blue Heron Diner

Approved

Filed Jun 5, 2026 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 5, 2026
Assembly type
RP
Serial number
A741687
Size
1 1/2
Test gauge serial
G-8544
Gauge calibration date
Dec 8, 2025
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.3 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-80-01214
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.