Back to the backflow review queue

Backflow assembly test: 6842 Meadow Lark Ct

Approved

Filed Nov 17, 2025 by Drew Stroud, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Nov 17, 2025
Assembly type
PVB
Serial number
W283298
Size
1
Test gauge serial
G-6646
Gauge calibration date
Jun 27, 2025
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Stroud, current on the service date
  • All required fields present
  • Address matches parcel 005-46-01130
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6842 Meadow Lark Ct
Owner: Logan Marsh
Parcel 005-46-01130