Backflow assembly test: 3190 Laurel Dr

Approved

Filed Aug 28, 2026 by Taylor Vance, Northstar Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Aug 28, 2026
Assembly type
RP
Serial number
A370251
Size
1
Test gauge serial
G-1260
Gauge calibration date
Dec 29, 2025
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Vance, current on the service date
  • All required fields present
  • Address matches parcel 005-59-01065
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.