Back to the backflow review queue

Backflow assembly test: 1297 Laurel Trl

Approved

Filed Apr 20, 2024 by Hayden Stroud, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Apr 20, 2024
Assembly type
PVB
Serial number
Z623868
Size
1
Test gauge serial
G-6423
Gauge calibration date
Sep 22, 2023
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Stroud, current on the service date
  • All required fields present
  • Address matches parcel 005-14-01269
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1297 Laurel Trl
Owner: Morgan Nguyen
Parcel 005-14-01269