Backflow assembly test: Main Street Bakery

Approved

Filed May 20, 2024 by Taylor Vance, Northstar Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
May 20, 2024
Assembly type
RP
Serial number
K577298
Size
1 1/2
Test gauge serial
G-8927
Gauge calibration date
Mar 24, 2024
Check valve 1
5.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Vance, current on the service date
  • All required fields present
  • Address matches parcel 005-48-01345
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.