Back to the backflow review queue
Backflow assembly test: 7193 Hickory Rd
ApprovedFiled Oct 17, 2024 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 17, 2024
- Assembly type
- DC
- Serial number
- W951276
- Size
- 3/4
- Test gauge serial
- G-4255
- Gauge calibration date
- Mar 29, 2024
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Benton, current on the service date
- All required fields present
- Address matches parcel 005-92-01199
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
7193 Hickory Rd
Owner: Parker Ramirez
Parcel 005-92-01199