Backflow assembly test: 7193 Hickory Rd
ApprovedFiled Oct 28, 2025 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 28, 2025
- Assembly type
- DC
- Serial number
- W951276
- Size
- 3/4
- Test gauge serial
- G-9127
- Gauge calibration date
- Aug 16, 2024
- Check valve 1
- 3.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.7 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Benton, current on the service date
- All required fields present
- Address matches parcel 005-92-01199
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.