Backflow assembly test: 8726 Turkey Hill Ln

Approved

Filed Jun 12, 2024 by Cameron Okafor, Northstar Backflow Testing. Filed from a phone.

Report

Date of service
Jun 12, 2024
Assembly type
RP
Serial number
Z342621
Size
1
Test gauge serial
G-3691
Gauge calibration date
Jan 11, 2024
Check valve 1
4.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
1.2 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Cameron Okafor, current on the service date
  • All required fields present
  • Address matches parcel 005-24-01054
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8726 Turkey Hill Ln
Owner: Cameron Vance
Parcel 005-24-01054