Backflow assembly test: 8726 Turkey Hill Ln
ApprovedFiled Jun 12, 2024 by Cameron Okafor, Northstar Backflow Testing. Filed from a phone.
Report
- Date of service
- Jun 12, 2024
- Assembly type
- RP
- Serial number
- Z342621
- Size
- 1
- Test gauge serial
- G-3691
- Gauge calibration date
- Jan 11, 2024
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Okafor, current on the service date
- All required fields present
- Address matches parcel 005-24-01054
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.