Backflow assembly test: 4344 Cedar Hollow Dr
ApprovedFiled Nov 5, 2025 by Drew Stroud, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 5, 2025
- Assembly type
- RP
- Serial number
- B180990
- Size
- 1
- Test gauge serial
- G-3677
- Gauge calibration date
- Jul 20, 2025
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 2.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Drew Stroud, current on the service date
- All required fields present
- Address matches parcel 005-15-01201
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4344 Cedar Hollow Dr
Owner: Parker Okafor
Parcel 005-15-01201