Backflow assembly test: 7542 Quarry Rd
Sent backFiled Nov 19, 2026 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 19, 2026
- Assembly type
- RP
- Serial number
- B510658
- Size
- 3/4
- Test gauge serial
- G-1100
- Gauge calibration date
- Aug 20, 2026
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Benton, current on the service date
- All required fields present
- Address matches parcel 005-13-01070
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Sent back Please add the test gauge calibration certificate.
Property
7542 Quarry Rd
Owner: Shawn Benton
Parcel 005-13-01070