Back to the backflow review queue

Backflow assembly test: 5911 Turkey Hill Ln

Approved

Filed Jan 15, 2026 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 15, 2026
Assembly type
RP
Serial number
W972154
Size
3/4
Test gauge serial
G-2138
Gauge calibration date
Apr 23, 2025
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-96-01080
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5911 Turkey Hill Ln
Owner: Taylor Nguyen
Parcel 005-96-01080