Backflow assembly test: Station Pizza
ApprovedFiled Nov 22, 2023 by Cameron Okafor, Northstar Backflow Testing. Filed from a phone.
Report
- Date of service
- Nov 22, 2023
- Assembly type
- RP
- Serial number
- W788307
- Size
- 1
- Test gauge serial
- G-6433
- Gauge calibration date
- Mar 17, 2023
- Check valve 1
- 5.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Cameron Okafor, current on the service date
- All required fields present
- Address matches parcel 005-17-01327
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.