Backflow assembly test: Station Pizza
ApprovedFiled Nov 17, 2024 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 17, 2024
- Assembly type
- RP
- Serial number
- W788307
- Size
- 1
- Test gauge serial
- G-2398
- Gauge calibration date
- May 22, 2024
- Check valve 1
- 4.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Benton, current on the service date
- All required fields present
- Address matches parcel 005-17-01327
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
3015 Old Church Rd
Owner: Ellery Holdings LLC
Parcel 005-17-01327