Back to the backflow review queue

Backflow assembly test: Station Pizza

Approved

Filed Dec 12, 2025 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Dec 12, 2025
Assembly type
RP
Serial number
W788307
Size
1
Test gauge serial
G-4321
Gauge calibration date
Apr 15, 2025
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-17-01327
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.