Back to the backflow review queue

Backflow assembly test: 7758 Hickory Trl

Approved

Filed Sep 7, 2026 by Hayden Stroud, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Sep 7, 2026
Assembly type
DC
Serial number
Z525070
Size
1
Test gauge serial
G-7941
Gauge calibration date
Jan 21, 2026
Check valve 1
4.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Stroud, current on the service date
  • All required fields present
  • Address matches parcel 005-57-01220
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7758 Hickory Trl
Owner: Parker Brandt
Parcel 005-57-01220