Backflow assembly test: 1205 Fox Run Rd

Approved

Filed Sep 7, 2025 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 7, 2025
Assembly type
PVB
Serial number
W913564
Size
3/4
Test gauge serial
G-4107
Gauge calibration date
Jan 3, 2025
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-36-01136
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1205 Fox Run Rd
Owner: Alex Ellery
Parcel 005-36-01136