Backflow assembly test: 3021 Mill Creek Ct

Approved

Filed Jan 29, 2025 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jan 29, 2025
Assembly type
RP
Serial number
Z892740
Size
1
Test gauge serial
G-9555
Gauge calibration date
May 9, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-50-01320
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.