Backflow assembly test: 8680 Quarry Rd
ApprovedFiled Feb 14, 2025 by Hayden Stroud, Keystone Backflow Testing. Filed from a phone.
Report
- Date of service
- Feb 14, 2025
- Assembly type
- PVB
- Serial number
- W999964
- Size
- 3/4
- Test gauge serial
- G-8650
- Gauge calibration date
- Dec 28, 2024
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Stroud, current on the service date
- All required fields present
- Address matches parcel 005-38-01334
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8680 Quarry Rd
Owner: Parker Lindqvist
Parcel 005-38-01334