Back to the backflow review queue

Backflow assembly test: Corner Animal Hospital

Approved

Filed Oct 21, 2026 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 21, 2026
Assembly type
DC
Serial number
Z618471
Size
1
Test gauge serial
G-5646
Gauge calibration date
May 1, 2026
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Taylor Benton, current on the service date
  • All required fields present
  • Address matches parcel 005-96-01315
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9884 Turkey Hill Trl
Owner: Lindqvist Holdings LLC
Parcel 005-96-01315