Backflow assembly test: 3700 Turkey Hill Ln
ApprovedFiled Nov 12, 2025 by Taylor Benton, Ridge Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 12, 2025
- Assembly type
- RP
- Serial number
- Z350881
- Size
- 3/4
- Test gauge serial
- G-9521
- Gauge calibration date
- Mar 22, 2025
- Check valve 1
- 3.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Taylor Benton, current on the service date
- All required fields present
- Address matches parcel 005-98-01227
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.