Back to the backflow review queue

Backflow assembly test: 7178 Old Church Ln

Approved

Filed Jan 3, 2026 by Hayden Stroud, Keystone Backflow Testing. Filed from a phone.

Report

Date of service
Jan 3, 2026
Assembly type
RP
Serial number
B678848
Size
3/4
Test gauge serial
G-4112
Gauge calibration date
May 6, 2025
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Stroud, current on the service date
  • All required fields present
  • Address matches parcel 005-15-01238
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7178 Old Church Ln
Owner: Rowan Whitcomb
Parcel 005-15-01238