Back to the backflow review queue

Backflow assembly test: 7233 Pine Knoll Trl

Approved

Filed Feb 24, 2026 by Jamie Harlow, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Feb 24, 2026
Assembly type
PVB
Serial number
A417494
Size
3/4
Test gauge serial
G-4338
Gauge calibration date
Aug 1, 2025
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Harlow, current on the service date
  • All required fields present
  • Address matches parcel 013-99-01155
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7233 Pine Knoll Trl
Owner: Jordan Hollins
Parcel 013-99-01155