Back to the backflow review queue

Backflow assembly test: 1463 Stone Gate Dr

Approved

Filed Apr 16, 2025 by Jamie Harlow, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Apr 16, 2025
Assembly type
RP
Serial number
A408499
Size
3/4
Test gauge serial
G-5168
Gauge calibration date
Jul 23, 2024
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Harlow, current on the service date
  • All required fields present
  • Address matches parcel 013-76-01119
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1463 Stone Gate Dr
Owner: Emerson Calloway
Parcel 013-76-01119