Back to the backflow review queue

Backflow assembly test: 4413 Quarry Ln

Approved

Filed Jul 25, 2026 by Hayden Danner, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jul 25, 2026
Assembly type
RP
Serial number
K937785
Size
3/4
Test gauge serial
G-4841
Gauge calibration date
May 31, 2026
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Danner, current on the service date
  • All required fields present
  • Address matches parcel 013-46-01342
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.