Backflow assembly test: 9212 Old Church Trl
Needs reviewFiled Nov 23, 2026 by Hayden Danner, Northstar Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 23, 2026
- Assembly type
- RP
- Serial number
- Z552830
- Size
- 3/4
- Test gauge serial
- G-7548
- Gauge calibration date
- Sep 9, 2026
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Danner, current on the service date
- All required fields present
- Address matches parcel 013-46-01326
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
9212 Old Church Trl
Owner: Casey Fairley
Parcel 013-46-01326