Back to the backflow review queue

Backflow assembly test: 7986 Quarry Rd

Approved

Filed Sep 3, 2024 by Logan Benton, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 3, 2024
Assembly type
RP
Serial number
W637377
Size
3/4
Test gauge serial
G-9454
Gauge calibration date
Mar 29, 2024
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Benton, current on the service date
  • All required fields present
  • Address matches parcel 013-85-01328
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7986 Quarry Rd
Owner: Shawn Harlow
Parcel 013-85-01328