Back to the backflow review queue
Backflow assembly test: Riverside Brewing Co
ApprovedFiled Jul 24, 2024 by Logan Benton, Patriot Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jul 24, 2024
- Assembly type
- RP
- Serial number
- K760361
- Size
- 2
- Test gauge serial
- G-7100
- Gauge calibration date
- Dec 9, 2023
- Check valve 1
- 8.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Benton, current on the service date
- All required fields present
- Address matches parcel 013-16-01170
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
980 Turkey Hill Trl
Owner: Danner Holdings LLC
Parcel 013-16-01170