Backflow assembly test: 8076 Spring Branch Dr

Approved

Filed Aug 26, 2024 by Hayden Danner, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 26, 2024
Assembly type
RP
Serial number
B817675
Size
3/4
Test gauge serial
G-9726
Gauge calibration date
Jul 14, 2024
Check valve 1
7.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Danner, current on the service date
  • All required fields present
  • Address matches parcel 013-53-01133
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.