Backflow assembly test: 1281 Spring Branch Dr

Approved

Filed Jun 16, 2024 by Hayden Danner, Northstar Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 16, 2024
Assembly type
RP
Serial number
B232818
Size
1
Test gauge serial
G-1332
Gauge calibration date
May 9, 2024
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Danner, current on the service date
  • All required fields present
  • Address matches parcel 013-20-01293
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1281 Spring Branch Dr
Owner: Hayden Lindqvist
Parcel 013-20-01293