Backflow assembly test: Station Animal Hospital

Approved

Filed Jun 9, 2024 by Logan Benton, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 9, 2024
Assembly type
RP
Serial number
B432609
Size
4
Test gauge serial
G-3288
Gauge calibration date
Aug 25, 2023
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Benton, current on the service date
  • All required fields present
  • Address matches parcel 013-27-01024
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.