Back to the backflow review queue
Backflow assembly test: 5118 Hickory Trl
ApprovedFiled Sep 20, 2023 by Hayden Danner, Northstar Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 20, 2023
- Assembly type
- PVB
- Serial number
- B886777
- Size
- 3/4
- Test gauge serial
- G-3367
- Gauge calibration date
- Jun 28, 2023
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Hayden Danner, current on the service date
- All required fields present
- Address matches parcel 013-46-01066
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
5118 Hickory Trl
Owner: Emerson Whitcomb
Parcel 013-46-01066