Backflow assembly test: 9428 Sycamore Dr

Approved

Filed Oct 23, 2025 by Jamie Harlow, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 23, 2025
Assembly type
RP
Serial number
B902364
Size
3/4
Test gauge serial
G-9872
Gauge calibration date
Jun 10, 2025
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Harlow, current on the service date
  • All required fields present
  • Address matches parcel 013-15-01329
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.