Back to the backflow review queue

Backflow assembly test: 874 Old Church Trl

Approved

Filed Jul 25, 2025 by Jamie Harlow, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jul 25, 2025
Assembly type
PVB
Serial number
A604378
Size
1
Test gauge serial
G-8218
Gauge calibration date
Dec 18, 2024
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jamie Harlow, current on the service date
  • All required fields present
  • Address matches parcel 013-22-01209
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

874 Old Church Trl
Owner: Emerson Benton
Parcel 013-22-01209